1.Online/backup mode optional

UPS works in ECO mode normally, and will automatically convert to AC inversion mode or battery inversion mode when output voltage is higher than set range or AC is off to guarantee the load will be supplied with uninterruptable power.
The cheap UK breitling replica watches with practical functions are suitable for daily wearing.

The Canada breitling replica watches can meet common demands. All the hot models are available.

 

2.Batch charging will improve the service life of battery

Solve the influence of floating charge on the service life of battery

 

3.Comprehensive battery protection improves the safety of the system

Battery cell protection – pressure release value/membrane design for battery cell;

Battery group protection – adopt BMU to guarantee the Li-battery operates stably and reliably

System protection – automatic battery inspection and discover faults and warm in time.

 

4.Excellent performance of Li-FE battery

High energy density – small size, light weight, supportive for wall installation

Good high and low temperature resistance performance- Li-battery can realize high-capacity discharging within -20 - +70℃ with good temperature performance

Super-long service life – circular service life is longer than 1000 times;

High-rate discharge performance – small capacity can solve large problems and the application is more flexible;

Safety – by strict short circuit tests and destructive test, it does not catch fire or explode;

Environmental protection – heavy-metal-free, non-toxic, pollution-free.

 

The AAA UK top Rolex fake watches at affordable prices are worth having!

For men and women, the best quality replica watches UK with Swiss movements can be best choices.

Set Module:

HT1000E

HT2000E

HT3000E

System capacity

1KVA/0.8KW

2KVA/1.6KW

3KVA/2.4KW

System efficiency

ECO Mode: ≥98%/Inversion mode:≥88%

Input features

Rated input voltage

220VAC(single-phase three wire system)

Rated of  input voltage

(120~288)VAC

Range of input frequency

(48~52)HZ

Input power factor

≥0.97(full load)

Output features

Output voltage

ECOoutput:200-240VAC,nversion output 220(±1%)VAC

Output power factor

0.8

Output wave

Sine wave

Output frequency

ECO Output:(48~52)HZ

AC inversion:(48~52)HZ

Battery inversion:(49.9~50.1)HZ

Current peak value ratio

3:1(Max.)

Wave distortion degree

Linear load, when in full load THD≤3%

Non-linear load, when in full load THD≤5%

Conversion time

Bypass mode → Battery mode, Bypass – inversion switching time <10ms

Battery mode →Bypass mode: <2ms

Overload capacity

Inverter: under AC inversion mode: when under 105%~125% rated load for 1min, the system will mark alarm and turn to bypass output; when the overload is eliminated, UPS can automatically turn back to inversion mode

ECO Mode: Make alarm under 95%-120% load, and turn to standby mode when the load is 120% larger (cut off the output); the status can be inquired by RS232

Complete set efficiency

Inversion output: ≥88% (Full load)

ECO Mode: ≥98% (Full load or full battery)

Output short-circuit protection

AC/Battery inversion: cut off inversion output and make alarm

ECO Mode: Over-current self-recovered safety +FUSE (fast fuse)

Internal protection

In case of internal failure of UPS (such as inversion/BUS motor, generator overheat), turn off the inverter, DC/DC boot and PFC boot circuits, turn to bypass output and display alarms.

Battery

Circular service life

More than 1000 times

Working temperature

-20℃~60℃

Working condition

Noise

≤45dBA (1m right ahead of panel)

Working temperature

-20℃~60℃

Altitude

The altitude shall be less than 1000m. When it is higher than 1500m, the set shall be used by reducing rated power.

Appearances

Net weight

9Kg  Excluding storage battery

Size (mm)W×D×H

440*400*88(2U)

Input socket

1 Piece

Output socket